• Clean Agent Hfc-227ea Fire Suppression System
  • Clean Agent Hfc-227ea Fire Suppression System
  • Clean Agent Hfc-227ea Fire Suppression System
  • Clean Agent Hfc-227ea Fire Suppression System
  • Clean Agent Hfc-227ea Fire Suppression System
  • Clean Agent Hfc-227ea Fire Suppression System

Clean Agent Hfc-227ea Fire Suppression System

Agent: FM200
Type: Pipeless
Object: Abce Fire
Size: 20~343L
Certification: CCCF, CCC
Effective Range: According Protect Room Size
Customization:
Gold Member Since 2007

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
ZQMP XX L
Retirement Life
10 Years
Cylinder Capacity
20~343L
Cylinder Material
Carbon Steel
Extinguishing Agent
FM200 Gas
Cylinder Color
Red
Stored Pressure
2.5 or 4.2MPa
Transport Package
Wooden Case
Specification
20ltr, 40ltr, 70ltr, 90ltr, 100ltr, to 343ltr
Trademark
WELFARE
Origin
Guangzhou
HS Code
842410000
Production Capacity
1000bottle /Set Per Month

Product Description

From 1998, We Design, manufacture, installation, Operation and Maintenance HFC-227ea Fire Suppression System

Design According to following Standard:
China GB795. GB79G, GB410, GB14104, NFPA-2001(U. S. A)
GA400-2002<<Testing Way and Performance of extinguishing system Parts >>
Inside Gas: UL EX6288 describled NFPA2001

Where to use:
Bank data room, gold house,
Painting lines
Generator room, motor room,
Switch board room
Transformer room
Computer and servor room
Communication room
Ware house
All the other place where can not put out the fire by water

Not suitable for extinguishing following fire
1. Oxidizing Chemical and mixture, such as
2. Activitly metal, such as potassium(K), magnesium(Mg), Zirconium( Zr), etc.
3. Metal hydroxide, Potassium hydride, Sodium hydride
4. Miscellaneous fire caused by decomposition Chemical, Such as Hydrogen oxide,

How the System Working

Gas storage cylinder; 20LTR, 30LTR, 40LTR, 60LTR, 70LTR, 100LTR, 120LTR, 150LTR, 180LTR, 250LTR, 343LTR,
Power Supply: DCV 24, 0.5A
Max Protective Area: 8 Zones (depend on designs)

Tree Actuated ways

Automatic Control:
Electric Manual Control: .
Manual emergent control: I

System classification
Unit independent system (picture No 1)

Means one Fire Suppression system only can protect a protection area. I
Combination and distribute system (picture No2)

Means one fire Suppression system protected several protection area.
Three Part Production constructed whole System

Extinguisher equipment
Cylinder +valve +electrical solenoid + pressure gauge+High pressure discharge hose, connecting pipe, manifold pipe, Liquid or gas no Return valve, pressure switch, selection valve ( in multi protection system ), flange, elbow and nozzle

FM200 GAS (Agent )

FIRE DETECTS AND ALARMS
Fire control panel +smoke and heat detectors
Fire alarm bell +manual button,
Light warning gas discharging
Before we make offer we need follow technical,
Room size: Length width height
Protected subject
Better submit drawing of project
We can send offer within 24 hours after received your informations.

PART 1 Extinguisher Equipment ( Cylinder Assembly and parts )
1, SYSTEM STORED CYLINDER
Applicate for filling FM200gas and pressurized nitrogen gas. The cylinder installed with cylinder valve and pipe net work. Normal will filled with hFC227ea gas, when the fire occur inside gas can be discharged by system works.
It is consist of cylinder, valve, internal syphon tube, gauge, filled with HFC-227ea gas, dry nitrogen. Name plated display the weight, density, charge and location.

Working pressure: 4.2 Mpa or 2.5Mpa
Discharge time: ≤ 10s
Filling desity: ≤ 950kg/m3
Polit valve powder supply: 6.0± 1.0 Mpa(20C)
System working power: AC 220V DC 24V 1A
System working pressure: -10c~55C
Max protected area: Max 800m² , max volume 3600m³
Working means: Manual, auto, and eletrical
Capacity: 20L, 40L, 70L, 100L, 120L, 150L 180L, 240lLTR, 343LTR

Other Parts: Cylinder valve, pilot cylinder, pressure switch, high pressure discharge hose, manifold safety valve, liquild one way valve, gas one Way valve

Cylinder valve

High pressure hose

Selection valve

Liquid check valve (liquid one way valve )

Gas check valve
Manifold Safety valve,
, ressure switch
Lpilot cylinder

For installation and Maintenance
Factory installation And Testing

This instruction base conditional Wofu present system, any renew without further Instruction,
Please contact Wofu for more details or newest technical...Clean Agent Hfc-227ea Fire Suppression System
Clean Agent Hfc-227ea Fire Suppression System
Clean Agent Hfc-227ea Fire Suppression System
Clean Agent Hfc-227ea Fire Suppression System

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now