Customization: | Available |
---|---|
Agent Weight: | 16.8kg |
Cylinder Size: | 80L |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
IG541 Fire suppression system parts
1.IG541 fire suppression system introduction: |
Mixed gas IG541 is made up of 52% 40% 40% nitrogen, argon, carbon dioxide mixture of
proportion by the steric (physical) way,in a short period of time after discharge to the protection
zone can make protection zone of the oxygen concentration is reduced to support combustion
under 12.5%, and burning fire smothering action implementation, on the other hand, according tothe long-term medical experiments prove that the human body in 12.5% oxygen concentration
and the concentration of 2% to 5% carbon dioxide environment breath, brain of oxygen and
at normal atmospheric environment (21% oxygen concentration and co2 concentration 0.03%)
gained by the oxygen content is the same. This is because in hypoxia environment, if carbon
dioxide concentrations increased to 2% 5% can make people breathing deepen and accelerate,
in unit time make the person obtains enough oxygen to brain cells. Mixed gas IG541, 8% of the
carbon dioxide gas is artificially make the protection zone of rising carbon dioxide levels to
meet the anoxic environment breathing for 2% 5%, and won't cause harm to human body.
1.1system structure
unit independent system
2.IG541 fire suppression system parts: |
All parts made of IG541 system:stored bottle,driving gas bottle,bottle rack, connecting pipe,safety relief device, Low leakage and high sealing valve,one way valve,manifold pipe,gas check pipe,pressure switch,nozzle, colleting of sewage,flange,square bent, pressure reducing device
3.IG541 fire suppression system unique advantages: |
1. Agent completely by nature exists in the atmosphere of inert gas, after the discharge to the
environment completely without damage;
2.Under prescribed fire extinguishing concentration is completely harmless to human body, can
stay in one place safely use;
3. Fire extinguishing agent sources, can ensure long-term use;
4.Fire extinguishing agent is completely composed of inert gas, does not cause protection zone
temperature fell sharply after discharge, the precision equipment and other valuable belongings
without any harm;
5. Because of the storage pressure is higher, compared with other fire extinguishing system can
transport a long distance,
6.Under the combined distribution system methods can connect more protection zone, thus
saving investment.
4.IG541 fire suppression system main technical parameters: |
20 °C storage pressure: 15 MPa
fire extinguishing agent storage bottles of specifications/filling quantity: 80l/16.8 Kg,
maximum working pressure (50 °C) : 17.2 MPa 1 start mode: magnetic start, mechanical
emergency start
electromagnetic drive air pressure: 6.0 + / - 1.0 MPa (20 °C)
electromagnetic drive starting power: DC24V / 1.5 A 1.2.7
agent application time: 60s or less
protection zone temperature: 0 °C to 50°C
store between bottle temperature: 0°C to 50°C
5.IG541 fire suppression system operation principle: |
1. mixed gas IG541 automatic fire extinguishing system with automatic, manual, mechanical
emergency operation three kinds of start ways.
2.condition automatically, if a protection zone occurs with smoke (or temperature), the protection zone, smoke fire detector (or temperature) movement and the fire alarm controller into a single
fire alarm, fire alarm controller that is into the single state, drive electric alarm signal of a single
fire alarm at the same time, this time will not start the fire extinguishing system of control
signals. As the spread of fire protection zone, the temperature rising smoke (or increase), the
other primary circuit heat or smoke fire detector, the controller into a single fire signal, the
controller immediately confirm that there is a fire, at the same time signal composite fire alarm
and linkage (closed air conditioning, ventilation device and fire damper, fire doors, fire shutter,
etc.). After 30 seconds of time delay, tThe controller output signal to start the fire extinguishing
system, cast into the fire extinguishing agent through the pipeline to implement fire protection
zone. Controller receives the feedback signal of pressure signal after the show bright deflated
lights, avoid straying. In manual mode, alarm controller only when the fire broke out a fire alarm
signals and does not produce linkage.
3. requires automatic or manual mode, the personnel on duty after confirmation of fire, press the alarm controller on the front panel or the scene of the "emergency start" button to start the fire
extinguishing system immediately. Before discharge control signal output, press the alarm
controller on the front panel or the scene of the "emergency stop" button, the system will not
discharge signal output.