CO2 fire extinguishing system stored cylinder
1.High-press CO2 Fire-extinguishing System Introduction: |
The carbon dioxide is liquidized by high pressure and stored in cylinders, when spraying the
carbon dioxide is expending sharply and absorbing a large quantity of heat, thus to reduce
the temperature of the fire scene and dilute the oxygen level of the protected zone so as to put
the fire out. Carbon dioxide is a inert gas, which is inexpensive, non-polluted, dissipated, and
traceless. The carbon dioxide fire extinguishing system is able to put gas fire out after the gas
supply source is cut, and it is also able to put out liquid fire, solid fire of fusible materials such as
paraffin and asphalt, solid surface fire, deep-seated solid fire such as wincey, fabric, and paper,
and electric fire, etc. The system is applicable to libraries, archives, database, bulk storages of
liquid, computer rooms, communication rooms, generator rooms, substation rooms, oil immersion
slots, mechanical mills, drying devices, and lacquer product lines. Note that carbon dioxide causes
asphyxiation and the system shall be used where no people are involved. If the system takes
effect in working places appropriate measures shall be taken to ensure safety.
The system puts out fires in a sealed room in a total flooding mode, it also works in a local
application mode to put out non deep-seated fire of protected objects where sealed rooms are
not required. The local application mode uses special nozzles which allow the extinguishing agent
acts fully on combustion object directly, the system keeps supplying extinguishing agent on the
combustion object for a certain time and intensity in order to put out the fire.
2.CO2 Gas cylinder technical parameters: |
Volume:70L;
Accessories: tank / valve/ internal siphon tube/flexible hose/gas check valve;
Tank size:1500* 267*5.7m(diameter*height*thickness);
Gas weight:45kg
Storage pressure(20):5.7MPa
Max working pressure(50): 14.4MPa
Painting: red epoxy polysteter RAL3000/red coating polyster RAL3000;
Valve size:brass,thread: PZ39, hose thread: G5/8, release pressure:19 ±0.95;
Container valve is consisted of valve body, starter device, piston, relief device, etc.
Extinguishing agent spraying time:≤60s;
Protective area temperature:0~50
Spraying leavings of cylinder:≤3Kg/bottle
MODEL |
70LTR |
WORKING PRESSURE (MPa) |
5.17 |
DICHARGE TIME (s) |
≤60 |
FILLING WEIGHT /BOTTLE |
42 |
CAPACITY (LTR) |
70 |
WORKING TEMPERATURE |
0~49 |
NOZZLE WORKING PRESSURE (MPa) |
≥1.4 |
LEAKAGE DECTOR |
10% |
HEIGHT OF PRECTED OF NOZLLE (m) |
0.3-6.5 |
SYSTEM ACTING MEANS |
AUTOMATICEMERGENCY MANUAL,MACHINICA |
EXTINGUISHING WAYSS |
TOTAL FLOODING,PART FLOODING |
SYSTEM WORKING POWER |
24V,1A |
WORKING RESSURE OF SELF RELEASE PRESSURE (MPa) |
15±0.75 |
ACTING PRESSURE OF CYLINDER SAFETY RELASE (MPa) |
7.0±0.35 |
RETARDING TIME OF SYSTEM (s) |
≤30 |
3.CO2 Fire suppression system accessories: |
Fire control panel syotistem, smoke/heat/phc detector system, alarm system(fire bell, manual call,video audio alarm),equipment, cylinder, valve, selective valve, liquid,che,preck pipessure switch,
nozzle, pipe, ect.
4.CO2 System order instruction: |
Case 1. If client can supply drawing layout.we can make free design and make offer to you within 24hours, pls send us your drawing room layout.
Case 2. If client has equipment list ?? pls contact us, we can make free design and make offer to you within 24hours
Case 3. No any drawing layout, no equipment list, then give us your room size : length Xwidth X height and door information.