High pressure MT5kg fire extinguisher co2
1.CO2 fire extinguisher Features and Applicated:
Clear idea, low toxic, quick extinguishing , no residual ,
For Initial Fire Caused by Liquid , gas , and electrial equipment
Safe for use on clothing , equipment , valuable document and foold
2. 5kg CO2 fire extinguisher Technical Data:
Capacity : 5+0.05kg
Cylinder Material: carbon steel CK45#
Agent: 99% pure co2
Cylinder Size: D152*H575mm
Cylinder Thread: PZ 27.8
Thickness: 5.0mm
Temperature Range: -30°C ~ + 60°C
Discharge Time: > 12S
Discharge Range: > 4m
Working Pressure: 80bar
Test Pressure: 250bar
Fire Class: 89B
3. 5kg CO2 fire extinguisher Accessories:
Brass valve with hanger loop, middle red handle, outlet thread: W21.8
Rubber hose with horn
Siphon tube, PVC, thread M10*1, length:500mm
Red round hook
Red plastic sealing
4.Packing for 5kg co2 fire extinguisher:
Min Order 200pcs; Delivery time: 20-30Days
DESCRIPITON |
PACKING/CTN |
QTY |
N.W |
G.W |
CBM |
CTN SIZE |
MT5 CO2 Fire Extinguisher, PZ27.8 |
1 |
18.00 |
18.50 |
0.025 |
69*21*17 |
5.CO2 fire extinguisher Operator Instruction:
1. Should wear a glove when using to avoid the skin touch horn and hose, to prevent frostbite;
2. Quickly take extinguisher at a site where 5 meters away from the fire;
3. Lay down the cylinder, pull out the safety pin;
4. Hold the handle with one arm and push the pressing handle with the other;
5. Aim the nozzle of the fire, sweep side to side;
6. Keep upright position during use, do not lying, upside down
6.Maintenance of co2 fire extinguisher:
1. Should store it in a cool, dry and ventilated place, keep away from the fire;
2. Check the weight by the weighing method every half a year;
3. Cylinder should be Hydraulic Tested every 5 years, qualified them can be used
4. Fire extinguisher maintenance and refill, should the qualified professional Fire
Maintenance Department be responsible for.
7.Loading and Shipment of Fire Extinguisher
Fire extinguisher are dangerous goods under IMO 1044 class 2.2 by international sea bureau so all the shipment must shipped as DG cargo.
1. All cartons must stick IMO green label.
2. All container must pull green net
3. Danger shipping mark "1044"
8.Quality Problems
1. quality problem from the shipping company
pls check the cargo quality once you discharge the container. any humidity damage from the shipping company must take photo and send within 5days when your get cargo, or before unload them
2. quality problem from WOFU
within 2month after get container, the supplier must send pictures or videos to WOFU, we would reply buyer within 2days, about the reason be caused and solution means.
if 10% quality problem, WOFU can retired the cargo in the fee from WOFU.
if only some parts problem, WOFU can discuss with buyer if client agree to accept by discount or by cash. if not, client can return or rechange the cargo by WOFU's fee.