Customization: | Available |
---|---|
Cylinder Size: | 4.5/7.5/10.5L |
Cylinder Inside Gas: | Nitrogen |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.FM200 fire system electromagnetic driving device usage: |
It is use for fm200 or co2 fire extinguishing system,to store starting gas (high-pressure nitrogen), can be started electrically or manual, releasing starting gas to open selector valve and
container valve. It has the function of sealing, releasing, filling, discharging for low pressure, pressure
indicating, etc.
2.FM200 fire system pilot cylinder structure: |
Consist of valve-actuated device and storage tank. The material of the valve-actuated device
is copper alloy, blade and diaphragm are stainless steel. The storage tank is rechargeable seamless steel
container. Its structure is exquisite, the operation is reliable and the drive current is low. As shown in below:
3.FM200 fire suppression system pilot cylinder main technical parameters: |
Model |
Capacity (L) |
Refilling Pressure (20ºC) |
Starter Power |
Outside Diameter (mm) |
Height (mm) |
Net Weight (Kg) |
Higbee (external thread) |
ZEPD6-4.5 |
4.5 |
6.0±1.0MPa |
DC24V/1.5A |
110 |
780 |
18 |
M14×1.5 |
ZEPD6-7.5 |
7.5 |
6.0±1.0MPa |
DC24V/1.5A |
150 |
800 |
20 |
M14×1.5 |
ZEPD6-10.5 |
10.5 |
6.0±1.0MPa |
DC24V/1.5A |
150 |
980 |
22 |
M14×1.5 |
4.FM200 fire suppression system pilot cylinder packing: |
Use wooden box to packing,fixed the cylinder,good protect the goods.